Specifications include, but are not limited to: 1. Install a new FEO-K1 fire recall switch and bezel in the hall station. The bezel shall be Red with the following markings: Bypass, Off, On. The key shall be removeable in the off and on positions only. 2. Connect the relay signals (provided by others) to the controller to enable recall by the fire detection system. 3. Install fire signage at all landings. The signage made of white plastic with red and black symbols containing three (3) flame emblems and “In Case Of Fire Emergency Use Exit Stairs” 4. The signage at the Phase One switch shall include instructions for Phase One On, Off and Bypass positions. 5. There shall be a pretest prior to scheduling the acceptance test with the State of Iowa Elevator Division. 6. Provide all necessary materials, labor and permits.