1. Generator Equipment to be provided a. 50kw 3P 277/480v Industrial stand by generator (see below*) b. 100A service-rated transfer switch, In-phase (see below**) c. Weatherproof enclosure d. Qty – 1 – Battery Group 31 e. Qty – 1 – Engine block heater f. Qty – 1 – 90 Amp 100% rated thermal magnetic circuit breaker g. Qty – 1 – Remote emergency stop button kit 2. Provide all required rigging. 3. Provide and install the required conduit, power wiring, control wiring, and start circuits from the generator to the transfer switch. 4. Install a concrete pad 5. Provide pavement cutting, and trenching where required for the propane line and electrical line 6. Provide factory-trained technicians to load the bank, test, and accept the generator. 7. Training 8. Labor 9. Freight *Quantity 1 - Industrial diesel engine-driven generator set with turbocharged 4-cylinder 4.5L engine, consisting of the following features and accessories: • Stationary Emergency-Standby rated • 50 kW Rating, wired for 277/480 VAC three phase, 60 Hz • Permanent Magnet Excitation • With an upsized 80 kW alternator • UL2200 • EPA Certified • Standard Weather Protective Enclosure, Steel o Industrial Grey Baked-On Powder Coat Finish • 24" 189 Gallon Double-Wall UL142 Base tank o Mechanical fuel level indicator gauge o Electronic fuel level sender o Emergency Vents • Power Zone 410 Digital Control Panel for Single Generators o NFPA 110 Capable o Temp Range -40 to 70 degrees C o UL6200 o C-ETL-US o CE o 128 X 64 Graphical Display with Heater Auto/Manual/Off modes