Specifications include, but are not limited to: Product (2) Two grinding or chopper style submersible wastewater sewage pumps each fitted with at least 110’ of power and control cable Cutting blades must be heat treated to a minimum of Rockwell C60, or equal Explosion proof, continuous duty submersible motor, tandem mechanical seals, moisture sensors, and internal thermostats required Duty Point 230v-3PH, 60Hz 750 gpm @ 30’ TDH Communications Pump control wiring compatible with existing City system (specifications can be provided) Pump monitoring relays shall be included for seal leakage and over temperature mounted into existing control panel Mounting & Installation Mated compatibility with standard Flygt guide rail system consisting of a 6” base elbow, cast iron, with 6” guide bracket Stainless steel lifting chains for 25’ wet well Complete full service removal of a single 30 HP Xylem pump and two 5 HP Xylem Pumps Complete full service installation of new pumps and appurtenances Full pump inspection and startup