Specifications include, but are not limited to: 1.Comply with TIA/EIA-568-B.1.2.Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices."3.Terminate all conductors no cable shall contain unterminated elements. Maketerminations only at indicated terminals.Cables may not be spliced. Secure and support cables at intervals not exceeding 304.inches (760 mm) and not more than 6 inches (150 mm) from enclosures.5.Install lacing bars to restrain cables, to prevent straining connections, and to preventbending cables to smaller radii than minimums recommended by manufacturer.6.Bundle, lace, and train conductors to terminal points without exceeding manufacturer'slimitations on bending radii, but not less than radii specified in BICSI ITSIM, "CablingTermination Practices" Chapter. Use lacing bars and distribution spools.7.Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cablebetween termination, tap, or junction points. Remove and discard cable if damagedduring installation and replace it with new cable.8.Cold-Weather Installation: Bring cable to room temperature before dereeling. Heatlamps shall not be used for heating