Buffaloe Road Aquatic Center Aerco Benchmark 1.5 LN HVAC Boilers (2) G-11-0407 G-11-0625 Preventative Maintenance Services 1. Flushing of pressure relief valves 2. Inspection of control linkages for burner 3. Test low water cut-off, trip, and other safety devices 4. Inspection of air damper 5. Inspection of valves on gas train 6. Lubrication of linkage bearings and motor bearings 7. Inspection of pilot light operation 8. Testing of flame detector output 9. Inspection of burner combustion settings and adjustment, as needed. 10. Inspection of fresh air and return air damper linkages. 11. Inspection and cleaning of condensate trap Annually, will be scheduled by COR Aquatics Superintendent Buffaloe Road Aquatic Center Aerco Benchmark 1.5 LN HVAC Boilers (2) G-11-0407 G-11-0625 Preventative Maintenance Services 1. Inspection of burner 2. Replacement of igniter-injector 3. Replacement of flame detector 4. Replacement of flame detector gasket 5. Replacement of gas injector gasket 6. Replacement of exhaust manifold seal 7. Replacement of burner gasket 8. Replacement of condensate trap O-ring 9. Replacement of condensate trap orifice gasket 10. Replacement of LWCO/Capacitor assembly Years 1,3,5 will be scheduled by COR Aquatics Superintendent.