Specifications include, but are not limited to: CABLE: 1/0 PRIMARY ALUMINUM WITH 220 MIL EPR INSULATION. INSULATION. CABLE TO HAVE FULL CAPACITY NEUTRAL CONSISTING OF 16, #14 AWG COPPER CONDUCTORS OR EQUIVALENT EQUALLY SPACED AROUND THE CONDUCTOR. CABLE TO HAVE EXTRUDED SEMI-CONDUCTING CONDUCTOR SHIELD AND INSULATION SHIELD. INNER SHIELD INSULATION AND OUTER SHIELD SHALL BE APPLIED IN ONE CONTINUOUS OPERATION. MINIMUM INSULATION THICKNESS SHALL BE NO MORE THAN 105% OF SPECIFIED THICKNESS. CABLE TO HAVE POLY-ETHYLENE INSULATING JACKET, 50 MILS MINIMUM THICKNESS FROM OUTSIDE OF CONCENTRIC WIRE TO OUTER CABLE SURFACE. PRODUCT SHALL BE MANUFACTURED & TESTED IN ACCORDANCE WITH THE LATEST REVISION OF AEIC CS8-00 DRAFT 8, ICEA S-94-649, NEMA Pub. WC8 NO INSULATION SUBSTITUTE WILL BE ACCEPTED. CABLE SHALL BE MANUFACTURED BY SOUTHWIRE, CABLEC, KERITE, OKONITE, PRIELLI OR APPROVED EQUAL. MANUFACTURER SHALL HAVE A PROVEN TRACK RECORD WITH EPR INSTALLATIONS OF AT LEAST 15 YEARS WITH MINIMAL INSULATION RELATED FAILURES. CABLE TO BE SUPPLIED IN UNBROKEN LENGTHS OF 2,500 FEET ON HEAVY DUTY NON-RETURNABLE WOODEN REELS. REEL DIAMETER NOT TO EXCEED 42" x 72". IFP #910 152 60010 40,000 FT