Specifications include, but are not limited to: A. AHU-02-01 (Lab) 1) Replace Pre Filters (8-24 x 24 x 2 MERV 8) 2) Inspect Final Filters, replace if necessary (8-24x24x12, MERV 14) 3) Lubricate Bearings 4) Clean Blower 5) Check Damper Linkages For Tightness 6) Clean Condensate Drain Pan 7) Inspect Chilled Water Coil 8) Clean Dust and Debris from inside and outside with a shop vac. Clean return air boxes with a damp rag or clean water. 9) Clean VFD Heat Sink 10) Adjust Heat Wheel Seals 11) Check Heat Wheel Motor Run Out 12) Blow Heat Wheel Media with Compressed Air 13) Check Media Tightness 14) Check Reheat Heat Exchanger and Pumps for Proper Operation 15) Check Glycol Percentage B. AHU-01-01 (VAV) 1) Replace Pre Filters (9-24 x 24 x 2 / 3-24 x 12 x 2 MERV. 8) 2) Inspect Final Filters, replace if necessary (9-24x24x12 and 3-24x12x12, MERV 14) 3) Clean VFD Heat Sink 4) Clean Blower 5) Lubricate Bearings 6) Check Damper Linkages for Tightness 7) Clean Condensate Drain Pan 8) Inspect Chilled Water Coil 9) Clean Dust and Debris from inside and outside with a shop vac. Clean return air boxes with a damp rag or clean water C. AHU-01-02 (UFAD) 1) Replace Pre Filters (2-24 x 24 x 2 / 3-24 x 12 x 2 MERV 8) 2) Inspect Final Filters, replace if necessary (2-24x24x12 and 3- 24x12x12, MERV 14) 3) Clean VFD Heat Sink 4) Clean Blower 5) Grease Bearings 6) Check Damper Linkages For Tightness 7) Clean Condensate Drain Pan 8) Inspect Chilled Water Coil 9) Clean Dust and Debris from inside and outside with a shop vac. Clean return air boxes with a damp rag or clean water D. 3-Mechanical Room Fan Coil Units 1) Replace Filters (2-36 x 10 x 1 / 2-24 x 24 x 2) 2) Lubricate Bearings 3) Clean Blower Wheel with Compressed Air 4) Replace Belt E. 6-Exhaust Fans (restroom, trash room, Lab 121 & 3 on Mech Tower) 1) Lubricate Bearings 2) Adjust Belt Tension 3) Tighten All Set Screws, Key Ways and Bearing Keepers 4) Clean Fan Motor and Fan 5) Replace Belts F. Pumps 1-9 1) Lubricate bearings 2) Lubricate Coupler 3) Check Oil Level 4) Run pump 3 manually to get some run time.