Specifications include, but are not limited to: Remove and replace (Quantity of 60) FSP‐951 smoke detectors Remove and replace (Quantity of 15) FST‐951R heat detectors Remove and replace (Quantity of 8) bulk packs of B300‐6‐BP detector bases Remove and replace (Quantity of 15) NBG‐12LX manual pull stations Remove and replace (Quantity of 5) FMM‐1 monitor modules Remove and replace (Quantity of 5) FRM‐1 relay modules Remove and replace (Quantity of 3) ISO‐X Isolation modules Work can be performed during normal business hours Mondays through Fridays excluding County observed holidays. Contractor shall replace devices as they are removed so the system can be re‐ enabled at the end of each day. All devices shall be installed to manufactures recommendations and specifications. Program fire alarm system as needed to accept and recognize new devices. Contractor shall test each device and the system at the completion of the project to assure all devices are working as required. Existing wiring to devices shall remain. Contractor is not responsible for replacing wiring to devices. Contractor shall take care not to damage surfaces such as walls, ceiling and floors, however contractor will not be responsible for patching and painting of walls and ceilings if needed due to device replacement. Contractor shall be responsible for any permits that are required for this project and all work shall meet all local codes. Provide a one‐year labor and materials warranty for project.