Specifications include, but are not limited to: 1. 12 37KVA, 12120B2CSP POLE TRANSFORMER STOCK # 1-20012; 2. 3 25KVA, DV120B2CS P POLE TRANSFORMER STOCK # 1-20021; 3. 2 50KVA, 34120B2 CSP POLE TRANSFORMER STOCK # 1-20053; 4 . 3 50KVA, DV240ACONV POLE TRANSFORMER STOCK # 1-21010; 5. 3 75KVA, 12277B2CONV POLE TRANSFORMER STOCK # 1-21020; 6. 2 50KVA, 12240ACONV POLE TRANSFORMER STOCK # 1-21113; 1. Type CSP, Class B2 single phase, 60 hertz mineral oil immersed, self cooled pole type distribution transformer. High voltage 12,470 GRDY/7200 with overload single lamp. Low voltage 120/240. 2. All requirements shall be in accordance with the latest revision of ANSI C57.12.20-1988 and these specifications. 3. High voltage insulation BIL level 95 kV at 12,470 GRDY/7200, insulation class 15 kV. Low voltage insulation BIL level 30 kV at 120/240, insulation class 1.2 kV. 4. Design shall pass short circuit criteria per latest revisions of ANSI C57.12.00-1987 and C57.12.90-1987. Tank withstand shall meet the latest revision of NEMA TR-1-1980, part 2, page 6, section D. Pressure relief valve shall meet the latest revision of ANSI C57.12.20-1988. 5. Tank finish shall meet or exceed the latest revision of ANSI C57.12.28-1988 and a direct blow of 160 inch-pounds per ASTM D-2794-69. Cover shall have an insulated coating capable of withstanding 15 kV per ASTM D149. kVA marking shall be below secondary bushings.