Specifications include, but are not limited to: Condition: new Size: Exterior: 18'-0'' x 9'-6'' x 9'-5'' or comparable Interior: 16'-2'' x 8'-2'' x 7'-6'' or comparable Storage Capacity: 34,000lbs or better 55-Gallon Drum Capacity: 32 or better Sump Capacity: 480 Gallons or better Snow Load: 40PSF or better Wind Load: 120MPH or better Floor Load: 250 PSF Seismic: Category C Construction: Galvanized Steel, 14ga or better Shielding: Two-hour bi-directional fire rated, weatherproof construction that meets or exceeds UL 263 and ASTM E-119 Insulation: Mineral wool or other non-flammable material: Minimum R-12 rating Roof system: 1-hour Per IBC Section 722, fire rated Class A flame spread rating or better Weatherproof construction, continuously welded seams Roof structural system fabricated from 4”x2”x1/8” tubing on 24” centers, welded to roof supports Roof supports:12ga or better HRS Steel roof with multiple layers of UL Listed fire resistant gypsum wall board lined on the interior with galvanized steel sheets. Assembly must meet or exceed UL 263 and ASTM-E119. Sloped roof to facilitate runoff away from doors and door(s) equipped with exterior rain shields Floor System: Grating and leak-proof spill-containment sump assembly 1” welded galvanized steel floor grating 6” deep leak proof secondary containment sump Sump: 10ga or better, continuously welded, acrylic alkyd enamel coated or comparable Floor system must comply with NAAM MBG 531 Building Base: Open channel construction Undercoating: I-Coal Tar or comparable corrosion-resistant coating Forklift pockets and hold-down brackets welded to building Static Grounding System: 3 interior grounding lugs, 1 exterior static grounding connection, 1 10-foot long 5/8” diameter copper-clad steel grounding rod and grounding lugs