Specifications include, but are not limited to: Control shall be a UL Listed 480 Volt 10HP duplex pump control panel. Square D Nema contractors and overloads and must be used for Pump control (no substitutions). Liquid level control shall be a transducer style and programmable for lead, lag and alternate control. 30mm Hand-Off Auto control for both pumps. Moisture sensing relay and thermal overload Monitoring w/ manual reset. High level alarm light. Two non-resettable hour meters. 30mm LED Run, fault indications for each pump. Control shall consist of dead front panel with all control switches and indications. New equipment must be wired and compatible with existing SCADA and/or Telemetry system currently in operation at station.