Specifications include, but are not limited to: 2.1 Minimum specifications: 2.1.1 floor plan 11’ 11” x 14’ 4” (ADA compliant for radius) 2.1.2 Two (2) toilet riser, seat and lid (ADA) 2.1.3 Two (2) Urinal (stainless steel) 2.1.4 ADA grab bars (placement and number of bars dictated by ADA code) 2.1.5 Toilet paper holders (able to hold three (3) standards rolls). 2.1.6 Two (2) waste clean out hatch 2.1.7 Two (2) concrete waste vaults- 1,000 gallon 2.1.8 Siding-barn wood light brown/tan color 2.1.9 Roofing-Simulated cedar shake (7/12 roof pitch) 2.2 Building Design Offered Vault Building Must: 2.2.1 Designed to withstand 350 pounds per square foot snow load. 2.2.2 Designed to withstand 400 pounds per square foot floor load. 2.2.3 Able to withstand the effects of 150 miles per hour (3-second gust) wind exposure C as defined in the International Building Code. 2.2.4 Able to withstand the effects of a seismic design category E earthquake as defined in the International Building Code. 2.4.5 Contain sweet smelling technology (SST) 2.4.6 All wall to floor interior surface seams shall have a minimum 1” radius coving made of high strength grout. 2.4.7 Bottom slope of 1” per foot from under the toilet riser out to the outside cleanout area. 2.4.8 24” diameter (minimum) lightweight manhole cover installed to the rear of the building. 2.4.9 The manhole covers should be raised, with the surrounding concrete sloped away using a minimum slope of ½” per foot. 2.4.10 12” diameter round pipes will be installed to vent the vault and the pipe shall be raised a minimum of 3’ above the highest point of the roof. 2.4.11 Vent pipes shall be straight up from the vault. Page 8 of 10 1.3 Building Finishes 2.3.1 Caulking service temperatures from -40ºF