Specifications include, but are not limited to: medium Voltage Oil Switch to upgrade campus circuits 2,3,& 4. 2.1 MANUFACTURERS A. Cooper, RVAC Series 10 and 11B 2.2 OIL SWITCH A. Cutout: ANSI/IEEE C37.44; sealed type. B. System Voltage: 12.47/7.2 kV, three phase, wye, 60 Hz. C. Maximum Design Voltage: 15 kV. D. Basic Impulse Level: 60 kV. E. Rated Continuous Current: 600 amperes. F. Interrupting Rating: 10,000 rms symmetrical amperes. G. Rated load-break, making, and short-time currents: ANSI/IEEE C37.44. H. Configuration: As indicated on Drawings and as described in the Section 01 1000 Scope of Work. I. All sources and tap connections shall have separate switches. All tap connections shall have ELSG fuse protection. J. See Section 26 0513 for modular terminations and lightning arrestors. 2.3 ACCESSORIES A. Grounding Kit: Ground Bar with clamps for each side. B. Fuses: Supplied and installed by contractor. C. Bushing Inserts: 600A inserts as required.