Specifications include, but are not limited to: Testing Specifications 30.11.2.1.NHDES Underground Storage Tank Facilities Env-Or 400 requires that all UST monitoring equipment be tested annually. Tank leak monitor testing at State facilities shall be conducted in accordance with Env-Or 406.13, and manufacturer’s recommendations. All testers shall be properly trained and manufacturer certified to conduct testing and must verify that the leak monitoring equipment is functioning in accordance with the original design parameter and within manufacturer’s requirements. 30.11.3. Annual leak monitor tests shall verify, at a minimum, the following conditions: 30.11.3.1.Leak monitor console assignments are correctly programmed and labeled. Included shall be verification that the NHDES required sensor or probe legend is posted at the monitoring console and correct; 30.11.3.2.Tank and piping sensors or probes are present and positioned in accordance with manufacturer’s requirements; 30.11.3.3.Brine level in the interstitial space is within the manufacturer’s operating range (if applicable); 30.11.3.4.All secondary containment is free of debris, water, and regulated substance; 30.11.3.5.All sensors or probes are in good condition, inspected, manually tested, confirmed operational; 30.11.3.6.Audible alarms are present and operational; 30.11.3.7.Visual alarms are present and operational. Where installed, the proper operation of remote annunciator strobe lights shall be verified; 30.11.3.8.Verify that the communication system, for example a modem, is operational for leak monitoring systems and will relay alarms to appropriate personnel and/or remote location(s) (if applicable); and 30.11.3.9.All secondary containment is continuously monitored (if applicable)...