Specifications include, but are not limited to: • The enclosure must have a 4' x 4' x 8' vestibule, with one interior shielded pedestrian door (leading into the main enclosure space) and one exterior shielded pedestrian door (leading to the exterior of the enclosure). Comply___________ Exception: ____________ • The entire enclosure must fit within a 13' x 17' area. Comply___________ Exception: ____________ • Additional features shall include interior lighting, integrated (shielded) fire suppression tie-ins, integrated (shielded) ventilation tie-ins, (2) shielded power filters, (2) shielded ethernet/fiber optic filters (Gigabit), (1) shielded fire alarm filter, and flat interior floor (e.g. tile, laminate, etc). Comply___________ Exception: ____________ • The structure must be tested and conform to, or exceed, the following standards: IEEE Std 299-1997, MIL-F-15733, ANSI/UL-1283, MIL-STD-220A, and UL 1283. Comply___________ Exception: ____________ • The enclosure must have a minimum attenuation performance of: Magnetic: 55 dB at 10 kHz, 90 dB at 200 kHz, 100 dB at 1 MHz Electric: 100 dB from 15 kHz to 100 MHz Planewave: 100 dB from 100 MHz to 1GHz Microwave: 100 dB at 10 GHz, 90 dB at 25 GHz Comply___________ Exception: ____________