Specifications include, but are not limited to: 1. Condenser System: (1) Two Cell-Cooling Tower Serving (2) Two 270 Ton Chillers a. Carbon Steel & PVC Open Loop b. (2) Two End Suction Variable-Speed End Suction Pumps c. Annual Makeup: 2,400,000 gal d. Cycles of Concentration: 2.5-3.5 (Based on Topeka City Water Quality) e. Volume: 5900 gallons f. Chemical Products: Scale & Corrosion Inhibitor, Oxidizing Biocide, Non-Oxidizing Biocide 2. Chilled Water System: (2) Water-Cooled 270 Ton chillers & (1) One 120 Ton Air Cooled Chiller a. Carbon Steel & Copper Closed Loop b. (3) Three Variable Speed End Suction Primary Pumps, (2) Two Variable Speed End Suction Secondary Pumps c. Annual Makeup: Unknown. Some water losses occur based on system makeup design. d. Contract Volume Losses Covered: 2,000 gallons e. Volume: 5250 gallons f. Chemical Products: Scale & Corrosion Inhibitor, Non-Oxidizing Biocide (if applicable) 3. Heat & Reheat Water System: (3) Three 1,500 MBH Condensing Boilers a. Carbon Steel & Copper Closed Loop b. (3) Three Variable Speed End Suction Primary Pumps, (2) Two Variable Speed End Suction Secondary Pumps c. Annual Makeup: <2000 gallons d. Contract Volume Losses Covered: 2,000 gallons e. System Volume: 2,100 gal f. Chemical Products: Scale & Corrosion Inhibitor, Non-Oxidizing Biocide (if applicable)