Specifications include, but are not limited to: A. Pump shall be of the in-line wet rotor design. Oil lubricated pumps and shaft coupled pumps shall not be accepted. B. The pump shall be a standard product of a single pump manufacturer. The pump, motor, and variable speed drive shall be an integral product designed and built by the same manufacturer. C. The enclosure shall be marked “Enclosure Type 2.” D. The pump shall be certified and listed by a Nationally Recognized Test Laboratory (NRTL) for U.S. and Canada to comply with: a. UL778 b. UL 60730-1A c. CAN/CSA No. 108 E. The pump shall be labeled on the nameplate as having an Energy Efficiency Index (EEI) of no greater than 0.20. 2.1.1 Ratings A. Maximum Pressure: 175 PSIG B. Minimum Media Temperature: 14 °F C. Maximum Media Temperature: 230 °F D. Maximum Sound Pressure Level: 43dB(A) E. Voltage: [1x115V +/-10%][1x208-230V +/-10%] F. Maximum Energy Efficiency Index: 0.20...