Specifications include, but are not limited to: Vendor to provide all materials and labor to replace boilers per the terms of this contract. Remove and properly dispose/recycle existing LES Inc. Model HW3-30 Boilers (2) including gas, water, power, venting, as required. Remove and properly dispose/recycle existing Power Flame Model JR30A-12 Gas Burners (2). Remove and properly dispose/recycle existing 2 HP 100 GPM Boiler Pumps. Furnish and install two condensing boilers containing the minimum standards listed below. 1200 MBH input. 1000 MBH output. Entering Water Temp 160°F. Leaving Water Temp 180°F. Working Pressure: 30 PSI. 208V/3Phase/60 Hertz. 90-99% Efficiency. Must fit thru a 36” wide opening. Furnish & Install two Gas Burners with minimum 7” w.c. pressure. Furnish & Install two Vertical In-Line 100 GPM variable speed Boiler Pumps.