Specifications include, but are not limited to: Provide UPS system inspection per manufacturer’s recommendations. The inspection may include but is not limited to: 1. Visual Inspection to include fans, capacitors, vents, lamps, wiring. Tighten loose connections or wires. 2. Infra-Red check to include fans, capacitors, heat syncs, power connections, breakers, fuses, transformers. Re-torque connections as necessary 3. Check the UPS Internal History and Alarm Log - Verify recent events 4. Check operating parameters on digital display 5. Check calibration – are meters working correctly 6. Power check – percentage load, KW, KVA 7. Check main system voltages and currents, Record measurements, Verify / calibrate system alignment with factory specification...