Specifications include, but are not limited to: (CU 104008) RISER CLASS METAL OXIDE VARISTOR SURGE ARRESTER WITH A RATED DUTY CYCLE VOLTAGE OF 10 KV (RMS) PER THE SPECIFICATIONS AND DEFINITIONS OF ANSI C62.11-1987. MAXIMUM CONTINUOUS OPERATING VOLTAGE SHALL NOT BE LESS THAN 8.4KV (RMS). ACCEPTABLE ARRESTER MODELS SHALL HAVE A DEMONSTRATED ABILITY TO MEET OR EXCEED ALL APPLICABLE REQUIREMENTS OF ANSI C62.11-1987: INCLUDING DUTY CYCLE PERFORMANCE; LOW-CURRENT, LONG DURATRION TESTS; AND HIGHCURRENT, SHORT DURATION TESTS. THE ARRESTER HOUSING SHALL BE MADE OF POLYMER OR SIMILAR MATERIAL, EXCLUDING PORCELAIN, THAT HAS DEMONSTRATED ULTRAVIOLET STABILITY. THE HOUSING SHALL BE IMPERMEABLE TO WATER. THE ARRESTER SHALL BE EQUIPPED WITH A GROUND LEAD DISCONNECTOR THAT IS SOLIDLY ATTACHED AT THE BASE OF THE HOUSING. THE ARRESTER SHALL BE FURNISHED WITH A BRACKED DESIGNED FOR CROSSARM MOUNTING (EEI-NEMA BRACKET). ALUMAFORM ARP-10B-1GB-4X1-4X GE 9L13BHCO10 GE 9L13DHC010 GE9L13GHC010 JOSLYN 8151C0010J001 TYPE ZJP MCGRAW EDISON AZR401B10 OHIO BRASS 221609 7324 OR APPROVED EQUAL; (CU 104082) 100 AMP, 15 KV, 110 KV BIL, OPEN TYPE CUTOUT COMPLETE WITH FUSE HOLDER AND PARALLEL GROOVE CLAMPS. *FUSE HOLDER TO USE SOLID BUTTON HEAD FUSE LINKS AND SHALL HAVE A CONTINUOUS CURRENT RATING OF 100 AMPRES. *FUSE HOLDER SHALL BE INTERCHANGEABLE WITH THOSE OF OTHER MANUFACTURERS WITH S&C TYPE XS AS STANDARD. *MINIMUM INTERRUPTING RATING SHALL BE 7,000 AMPRES SYMMETRICAL AND 10,000 AMPRES ASYMMETRICAL. *LOWER HINGE AND TRUNNION SHALL BE CONSTRUCTED OF BRONZE. *EACH UNIT TO BE SUPPLIED WITH EEI-NEMA CROSSARM MOUNTING BRACKET. *THE CUTOUT SHALL BE EXCLUSIVELY OF THE POLYMER-INSULATED STYLE AB CHANCE ALUMA-FORM CSG-15-100A-110-CB-10KA COOPER POWER SYSTEMS S4B1P1A HUBBELL CP710-112PB S&C ELECTRIC OR APPROVED EQUAL; (CU 105497) 15KV LOADBREAK CONNECTOR KIT FOR USE ON 2/0 AWG COPPER, 15KV, 220 MIL INSULATION WALL THICKNESS, JACKETED CONCENTRIC NEUTRAL CABLE. THE CONNECTOR SHALL MEET THE REQUIREMENTS OF ANSI/IEEE 386 AND IEEE 592 LATEST REVISIONS. THE VOLTAGE RATING OF THE CONNECTOR SHALL BE 8.3/14.4 KV. THE CONTINUOUS CURRENT RATING SHALL BE 200 AMPERES. THE CONNECTOR SHALL BE DESIGNED FOR USE ON CABLE WITH A NOMINAL DIA. OVER INSULATION OF .905 INCHES AND A NOMINAL DIA. OVER INSULATION SHIELD OF 1.005 INCHES. *ELBOW TO INCLUDE CAPACITIVE TEST POINT. CONNECTOR KIT TO INCLUDE CONNECTOR BODY, BIMETALLIC COPPER TOP CONDUCTOR CONNECTOR, TIN PLATED COPPER PROBE, LUBRICANT, PROBE INSTALLATION TOOL, AND INSTALLATION INSTUCTIONS. COOPER LE215CC07T COOPER LE215CO7T ELASTIMOLD 166LR-C-5250 ELASTIMOLD 166LRC-0250 HUBBELL 215LE56T RTE/COOPER LE215COOT W/ 2639043A07B OR APPROVED EQUAL; (CU 108033) BASE AND T-SLOT KIT FOR CONDUIT STAND-OFF BRACKET ASSEMBLY. BASE TO PROVIDE 9" CLEARANCE FROM POLE FACE FOR MOUNTING RISER CONDUIT. T-SLOT CHANNEL SHALL BE 12" LONG TO ACCOMMODATE MOUNTING 1"-2" THROUGH 6" RISER CONDUIT. KIT TO INCLUDE ALL NECESSARY HARDWARE TO MOUNT T-SLOT CHANNEL TO BASE.BAR IS 12 INCH WITH BRACKET BEING 9 INCH. AB CHANCE ALUMAFORM 9-CSO-12-4WT OR APPROVED EQUAL