Specifications include, but are not limited to: A. Front Accessible Switchboards: 1. Main Devices: Fixed, individually mounted. 2. Branch Devices: Panel mounted. 3. Section Alignment: Front and Rear aligned. B. Nominal System Voltage: 208Y/120 V, 3∅, 4 wire. C. Main-Bus Continuous: 2000. D. Provide reduced energy maintenance switch on main breaker to have LS16 trip functions. E. All breakers to be rated 65 KAK minimum. F. Indoor Enclosures: Steel, UL 50E, Type 1. G. Enclosure Finish for Indoor Units: Factory-applied finish in manufacturer's standard gray finish over rust-inhibiting primer on treated metal surface. H. Barriers: Between adjacent switchboard sections. I. Insulation and isolation for main and vertical buses of feeder sections. J. Utility metering compartment. K. Customer metering compartment. L. Bus transition and incoming pull sections. M. Removable rear doors and compartment covers. N. Hinged front panels. O. Buses and Connections: Three phase, four wire unless otherwise indicated...