Specifications include, but are not limited to: Furnish and Install two (2) New Liebert five (5) Ton CRAC (Unit Model # PX018DA1CD09N7) for total of ten (10) Tons of Capacity. (Liebert Manufacturer product and model numbers will only be accepted) The unit will be placed in the current Server Room on the 1st Floor of the building adjacent to the existing five (5) Ton Liebert Unit. Furnish and install new Floor Stand Kits. Modify/Construct Existing Floor to accommodate Floor Stand Kits Furnish and install Leak Detection Kits. Provide/install/Extend PVC Condensate drains to existing floor drain. Provide/install/Extend the electrical wiring from the existing electrical panel. Furnish Provide/install/Extend two (2) New Liebert five (5) Ton ACCU Air Cooled Microchannel Condenser, (Model MCM040E1YD0XG2). (Liebert Manufacturer product and model numbers will only be accepted). In the lower-level loading dock exterior area, suspended by all thread Rod and Unistrut Under Concrete Overhead structure, Horizontal air flow position. Page 8 of 39 Provide/install/Extend interconnecting ACR Refrigerant Hot Gas and Liquid piping for each system. Provide/Install ½” Wall Armaflex (or equivalent) pipe insulation on both liquid and hot gas piping, add on insulation located on piping on the exterior of the building. Provide/install/Extend all interconnection power and control wiring. Perform Standing pressure test with Nitrogen. Evacuate Refrigerant circuits. Charge Refrigerant circuits with New Refrigerant.