Specifications include, but are not limited to: Relay Panels: Two-column 24” open rack mount type, free-standing, with rear wings to accommodate field wiring, terminal blocks and fuse blocks. The two sections shall be mechanically interconnected to form a single assembly. The panels shall be shipped as a single unit, with all internal wiring between sections completed and tested in the factory prior to shipment unless specifically approved in writing by the OWNER. Protective and Auxiliary Relays, General Requirements: Utility-grade, type as indicated. Relay configuration and programming provided by others. Transformer Protection Relay: Microprocessor-based, digital relay providing transformer differential, overcurrent and other features as specified below. Relay shall be Schweitzer SEL-787. Transformer Backup Overcurrent Relay: Microprocessor-based multifunction overcurrent relay. Relay shall be Schweitzer SEL-751. Transmission Line Relay: Microprocessor-based multifunction distance relay. Relay shall be Schweitzer SEL-311C. Power Quality Meter: Microprocessor-based multifunction power revenue and quality meter. Device shall be Schweitzer SEL-735. Lockout Relays: Electroswitch Series 24, no substitutions. 48 V DC trip coil, hand reset. For each relay provide quantity of contact decks indicated on the Drawings. Auxiliary Equipment: Universal Mounting Brackets: Arranged inside relay panels for mounting and wiring auxiliary devices; located to allow access to the back of the equipment mounted on front of panels. Panel space not utilized by equipment shall remain clear for addition of possible future equipment. Panel Wiring: