A. Where indicated, furnish and install an indoor dead front type, completely metal enclosed, low voltage, self-supporting switchboard structure independent of wall supports. Voltage rating shall be as indicated on the drawings. It shall consist of the required number of vertical sections bolted together to form one rigid switchboard with a nominal height of 90 inches. The sides and rear shall be covered with removable screw-on plates having formed edges all around. B. Equipment shall comply with the latest applicable standards of NEMA, ANSI and UL. C. Utility Metering Compartment: Fabricated, barrier compartment and section complying with utility company's requirements. If separate vertical section is required for utility metering, match and align with basic switchboard. Provide service entrance label and necessary applicable service entrance features. Include where indicated on the electrical one line diagrams. D. Small wiring, necessary fuse blocks and terminal blocks within the switchboard shall be furnished as required. All groups of control wires leaving the switchboard shall be provided with terminal blocks with suitable numbering strips. E. Switchboards shall be provided with adequate lifting means and shall be capable of being rolled or moved into installation position and bolted directly to the floor without the use of floor sills. F. All exterior and interior steel surfaces of the switchboard shall be properly cleaned and finished with gray baked enamel over a rust-inhibiting phosphatized coating. Color shall be ANSI 49 or ANSI 61, gray...