1. Provide, erect, and maintain lights, barriers, weather protection, warning signs, and other items as required for proper protection of building tenants, visitors and all workers engaged in Elevator Modernization, either directly or indirectly for the Elevator Modernization. 2. Provide machine room mechanical ventilation (HVAC) to maintain temperature at not more than ninety-five degrees Fahrenheit (95° F), for ninety-five percent (95%) of the time, unless a lower temperature is specified by the elevator equipment manufacturer. 3. Fire/Life Safety: a. Provide and interface Recall Initiating Devices in all elevator lobbies and elevator machine room. 4. Lighting: a. Provide LED illumination in the elevator Pit sufficient to meet code requirements, currently a minimum of 10 fc. 5. Provide one (1) 15A-120VAC fused circuit lockable disconnect in the elevator Machine Room for the intercom. 6. Provide GFCI receptacles in elevator Machine Room and Pit. 7. Provide conduit for phone line from machine room j-box to elevator controller. Elevator Contractor to provide labor/material to hook up the telephone wires from J-box to new elevator controller. Owner to provide phone line to elevator machine room...