3000 Feet SECONDARY URD CABLE--INSULATE ALL CONDUCTORS WITH 600 VOLT CROSS-LINKED POLYETHYLENE. ALL CONDUCTORS ARE CONCENTRICALLY STRANDED COPPER WITH CLASS B STRANDING PER AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) STANDARD B8. ASSEMBLE TWO (2) #4/0 AWG CONDUCTORS TOGETHER WITH ONE (1) #2/0 AWG CONDUCTOR. THE CONDUCTORS SHALL BE RATED WITH A MAXIMUM OPERATING TEMPERATURE OF 90 DEGREE CENTIGRADE IN EITHER WET OR DRY USE. COMPLY WITH UNDERWRITERS LABORATORIES (UL) STANDARD UL 854 FOR USE-2 CABLE OR UL 44 FOR RHW-2. ¿UNIQUELY LABEL EACH 4/0 CONDUCTOR. 2/0 CONDUCTOR SHALL HAVE YELLOW STRIPE.¿ . FURNISH THE CABLE ON A STANDARD NONRETURNABLE REEL WITH 1000 FEET PER REEL. TAG EACH REEL WITH TOTAL FEET, GROSS, TARE, NET WEIGHT, TYPE OF CONDUCTOR, NUMBER OF CONDUCTORS, AND MANUFACTURER. 25 Each - (CU 102153) 5/8" X 12" HOT DIP GALVANIZED STRAIGHT THIMBLE EYE BOLTS, WITH ONE (1) NUT EACH, MEETING ANSI/NEMA STANDARDS. 100 Each: - (CU 102288) SADDLE TYPE CROSSARM PIN WITH 1" LEAD THREAD FOR 3-3/4" X 4-3/4" WOOD CROSSARM, SUPPLIED WITH TWO (2) 5/8" X 7" CARRAGE BOLTS, TWO (2) 5/8" SQUARE NUTS, TWO (2) 5/8" MF LOCK NUTS, AND WASHER PLATE. TO BE HOT DIP GALVANIZED. - (CU 103380) INSULATED NON-TENSION COMPRESSION SPLICING SLEEVE FOR NO. 1/0 STRANDED ALUMINUM PHASE WIRE IN TRIPLEX SERVICE CABLE, INHIBITOR FILLED, EXTRUDED NYLON COVER, BOTH SIDES SIZED FOR 1/0 STRANDED CONDUCTOR, FOR INSTALLATION WITH 5/8 DIE. 15 Each - (CU 106220) 15 AMP TYPE "K" EEI-NEMA FUSE LINKS.