▪ Laboratory Tests • Air Infiltration Test in accordance with ASTM E 283 at a test pressure of 1.57 psf. For both fixed units and operable units, the air infiltration rate should not exceed 0.3 ft3 /min/ft2 • Water Infiltration Test in accordance with ASTM E 331 and ASTM E 547 at a test pressure of 15% the design pressure, as well as local weather condition which in this case is 5.3 psf. The window systems must have no leakage when tested at 5.3 psf. ▪ Field Tests • Testing of mock-up installations that include all representative components of each system: o Window/curtain wall head, jamb, sill, intermediate rail and mullion components, as well as all types of intersections and connections. o Window/curtain wall interfaces with surrounding construction, including precast concrete panels, cement plaster, metal siding, sealants, etc. o Note: mock-up will be installed in Treasure Island. • The performance criteria should be as follows: o Air Infiltration Test in accordance with ASTM E 783 at a test pressure of 1.57 psf. For both fixed units and operable units, the air infiltration rate should not exceed 0.3 ft3 /min/ft2...