• Extend Existing Jail Tridium N4 Building Automation System with Honeywell Webs w/Alert on BTI Smoke Control • Verify hardware and software license needed to extend existing system to new devices • Retrofit the following siemens MBC Panels with updated DDC/Smoke Control IO Controllers. o (8) Siemens MBC Panel Number 1, 2, 3, 6, 7, 8, 9, and 12. o Re-Use Existing Control Panels and End Devices. • Integrate (245) existing Siemens TEC’s for terminal HVAC equipment o Existing Siemens TEC Controllers to Remain with Existing Programming. o Siemens TEC Controllers Reside Under MBC Numbers 1, 2, 3, 6, 7, and 12. o Re-Use Existing Controllers, Control Panels, and End Devices. • Retrofit the following Siemens MEC Panels with updated DDC/Smoke Control IO Controllers. o (1) Siemens MEC Panel Number 5 o Re-Use Existing Control Panels and End Devices. • Retrofit the following Siemens RBC Panels with updated DDC/Smoke Control IO Controllers. o (1) Siemens RBC Panel Number 4 o Re-Use Existing Control Panels and End Devices. • Create new graphical user interface for all equipment. o Graphical User Interface to match existing county graphical user interface. o Note: multiple graphical user interfaces exist; match Jail facility staff preference. • Create new 3-D floor plans for all areas of the Jail. o 3-D Floor Plan to Match Existing County Floor Plans. o Note: multiple 3-D floor plans exist; match Jail facility staff preference.