One Union Ave Data Center: Two (2) Liebert CRV Air-Cooled Cooling System, with the following features: Nominal 35kW, 120 kBtuh at approximately 90F, 27% RH 208 Voltage, 3 Phase, 60 Hz Condensate Pump 65k SCCR Liebert iCOM control system with 9” Color Touch Display 2T temperature sensors to measure air temperature entering server racks Variable speed EC plug fans Digital scroll, variable capacity compressor Electric Reheat Steam Generating Humidifier Locking Disconnect Switch Liebert IntelliSlot Unity Monitoring Card (1) LT460-Z20 Zone Leak Detection Sensor Unit to be located within a row of heat generating IT equipment racks. Liebert MC Air-Cooled Microchannel Condenser Warranty Inspection / Supervised Start Up Services during normal business hours 8x5 Freight included to New Haven, CT One (1) 40kVA / 40kW Liebert EXM UPS System, with the following features: 40kW Capacity using 20kW power modules (20kW +1 Redundant when load is less than 20kW) System input and output = 208/120V, 4W+G Monitoring Cards for ethernet/SNMP/Modbus/Bacnet/Output Dry Contacts 9 Minute battery system at full 40kW load and 22 minutes at 20kW load. Batteries are standard 12V VRLA type, internal to UPS cabinet to save on floor space, with isolation breaker External Maintenance Bypass Cabinet – 3-Breaker with SKRU (Key Interlock), mounted to side of UPS cabinet Factory Testing with Certified Test Reports On Site Start Up Services, scheduled 7x24, by manufacturers technician Freight included to New Haven, CT Wintergreen Data Center: Two (2) Liebert CRV Air-Cooled Cooling System, with the following features: Nominal 35kW, 120 kBtuh at approximately 90F, 27% RH 208 Voltage, 3 Phase, 60 Hz Condensate Pump 65k SCCR Liebert iCOM control system with 9” Color Touch Display 2T temperature sensors to measure air temperature entering server racks Variable speed EC plug fans Digital scroll, variable capacity compressor Electric Reheat Steam Generating Humidifier Locking Disconnect Switch Liebert IntelliSlot Unity Monitoring Card (1) LT460-Z20 Zone Leak Detection Sensor Unit to be located within a row of heat generating IT equipment racks. Liebert MC Air-Cooled Microchannel Condenser Warranty Inspection / Supervised Start Up Services during normal business hours 8x5 Freight included to New Haven, CT One (1) 40kVA / 40kW Liebert EXM UPS System, with the following features: 40kW Capacity using 20kW power modules (Field Scalable to 60kW total capacity) System input and output = 208/120V, 4W+G Monitoring Cards for ethernet/SNMP/Modbus/Bacnet/Output Dry Contacts 14 Minute battery system at full 40kW load (7 Minutes @ Future 60kW Load). Batteries are standard 12V VRLA type, external in matching battery cabinet External Maintenance Bypass Cabinet – 3-Breaker with SKRU (Key Interlock), mounted to side of UPS cabinet Factory Testing with Certified Test Reports On Site Start Up Services, scheduled 7x24, by manufacturers technician Freight included to New Haven, CT