A. Electrical System AC and DC - All cables will be checked, cleaned and tightened as required. Batteries will be checked for correct specific gravity and distilled water added if necessary. Inspect and test battery charger and/or battery charging alternator for proper operation. Check all breakers, terminations, control panels, control components, warning systems and emergency shutdowns for proper operation. B. Fuel System - With the generator set operating, inspect all fuel lines, filters, and fittings for tightness and any fuel leaks. C. Lube Oil System - D. Check oil level and record engine oil pressure. Inspect complete lubricating system for leaks. If unit has lube oil heater, check to insure it is operating properly. E. Cooling System - Inspect system for leaks and test coolant for proper coolant mixture and the supplemental coolant additives as recommended by the engine manufacturer in order to maintain a properly balanced cooling system to prevent corrosion, scaling, and premature seal failures. Add coolant mixture as needed. Inspect block heater and connections for proper operation and leaks. Also, inspect all hoses, hose clamps, belts, for leaks, cracks, fraying or any other damage...