The purpose of this Request for Bids (RFB) is to solicit bids from qualified firms to install a new 1000-amp service and terminations for our Plastics Engineering lab at our Tech Center location. 3.1 Provide and install (1) 1000A main breaker NEMA 1 3 phase 4 wire 480Y/277V MDP service rated panel. Provide and install (1) 3 pole 35A breaker. Provide and install (1) 3 pole 250A breaker. 3.2 Provide and install (2) 4” PVC conduits on the exterior of the building and connect to (2) existing 4” PVC conduits. Provide and install (2) 4” EMT conduits inside of building to new MDP panel. Provide and install (2) sets of copper THHN in each 4” conduit from exterior service transformer to new MDP panel. 3.7 Terminations at transformer done by others. Provide terminations at CT cabinet and new MDP panel. Provide and install conduit, THHN green wire and terminations for building steel grounding per NEC. Provide and install conduit, THHN green wire and terminations for water main grounding per NEC. 3.4 Provide wire and terminations for transformer bonding ground per NEC. Provide coordination study on the below equipment per NEC. 3.5 Equipment to Be Tested Per the Following One‐Line(s)/Drawings: Panelboards & Switchboards – NETA ATS 7.1