Model Eaton 9355 Cabinet Style 3 High w/ 64 Battery Power Ratings 15 KVA / 13.5KW @ 0.9 P.F. Topology Double Conversion Input Input Voltage 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye Input Frequency 60 Hz ± 5 Hz Voltage Correction Range 176-228.8V AC Power Factor (Full Load) 0.99 typical Output Waveform (On-Line) Sinewave Waveform (On-Battery) Sinewave Output Voltage (RMS) 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye Output Frequency 60 Hz Efficiency (Full Load / On-Line) 91% typical Voltage Regulation ± 1% Input Current Distortion <= 5% THD Overload Capabilities 125% (1 min.) / 150% (5 sec.) / 110% (10 mins.) Battery Battery Type VRLA, 9AH, maintenance free (Field replacable) Typical Backup Time (Full Load) > 70 min @ full load (> 8 hours @ 15% full load) External Battery Cabinet (EBM) Configuration EBM 96 (Qty 2 for BY unit only) (Knotts St. unit = Qty 0) Operation / General Diagnostics Full system self-test @ startup UPS Bypass Automatic on overload or UPS failure On-Line Transfer Time 1 ms typical Audible Noise (Full Load @ 1m) < 58 dBA Communications Minimum Requirements Graphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card (INDGW-X2 Industrial Gateway Card) Network type Factory Installed MS Network Card (SNMP) Certifications Quality ISO 9001 Warranty Standard 1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification. Customer Service Initial Start Up Vendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Byron Nuclear Generating Station and Knotts St. GEMS Test Bay in Springfield, IL. Tech Support Availability 24/7 (Unlimited)