1-Square D Custom Swbd Series 2-QED-2 Switchboard --------------------------------- Square D Custom Swb Series 2 Designed and Tested in accordance with: UL 891/NATIONAL ELECTRIC CODE/NEMA PB-2 System Voltage - 480Y/277V 3Ph 4W 60Hz System Ampacity - 1600A Source Description - Single Main Bussing – Aluminum Plated w/Tin and Copper Plated w/Silver Neutral Bus - 100% Max Available Fault Current (RMS) - 65kA Enclosure - Type 1 Accessibility: Front Only Exterior Paint Color - ANSI 49 Ground Lug provided for each device SIS Control Wire Aluminum Ground Bus Dimensions --------------------------------- 2 - 36" Wide Section(s) 2 - 24" Deep Enclosure(s) Dimensions: 72.00" W X 24" Max D X 91.5" H Approximate Weight: 1639.00 lbs / 743.45 kgs Incoming Requirements --------------------------------- Suitable for Use As Service Entrance Entry Point: Left of Lineup, Through the Top Connection Type: Cable Mains --------------------------------- 1 - 1600AS/1600AT 480V 80% Rated 65 kA 3 Pole UL, Fixed Mounted Electronic Trip Circuit Breaker: Type RK Power Trip Unit, Long Time, Short Time, Instantaneous, Ground Fault Kirk Key Interlock Energy Reduction Maintenance Switch Feeders --------------------------------- 1 - 150AT 480V 80% Rated 100 kA 3 Pole UL, Group Mounted Thermal Magnetic Circuit Breaker: Type HL 4 - 200AT 480V 80% Rated 100 kA 3 Pole UL, Group Mounted Thermal Magnetic Circuit Breaker: Type JL 3 - 400AT 480V 80% Rated 65 kA 3 Pole UL, Group Mounted Basic Electronic Trip Circuit Breaker: Type MJ 1 - 600AT 480V 80% Rated 65 kA 3 Pole UL, Group Mounted Basic Electronic Trip Circuit Breaker: Type MJ 1 - 100AT 480V 80% Rated 65 kA 3 Pole UL, Group Mounted Thermal Magnetic Circuit Breaker: Type BJ