1. HVAC UNIT Specifications Remove old (2008 Carrier unit) and dispose of old equipment. Replace with new Water Source Heat Pump rooftop unit on a curb adaptor. Modify electrical and water piping as needed to make new connections. Once installation is complete, system operations will be tested. Unit Specifications Rooftop Water Source Heat Pump R-454B 20 Ton 460/60/3 Symbio 700 Econimizer, DB with Barometric Relief Multi Speed Motor Hinged Access Panels with 2-in MERV 8, one set Advanced Controls and BACnet BAS Standard Refrigeration Option Condensate Overflow Switch (COS) Stainless Steel Drain Pan Insulated Copper-Water Coil 35F Freezestat (For Water Loop) CO2 kit with wall mounted sensor (Fld) Proposal Form City of McMinnville Parks and Recreation Department HVAC Unit