A. Provide three (3), 480V, electric, factory assembled, centrifugal chillers complete with compressor, motor, unit mounted variable speed drive (VSD)/adjustable frequency drive (AFD), evaporator, condenser, microprocessor controls, graphics and all required ancillary equipment including mobile refrigerant pump out unit. The chillers shall be configured as a simplex compressor unit with integrated controls and will be field installed to operate in a headered, variable primary chilled water pumping system. The chillers will also be connected to a new headered condenser water system. B. Each chiller shall have a guaranteed capacity of 1,400 tons at the design conditions that are listed in the table in Part 5 of this section. C. Based on space limitations within the existing ECP, the maximum chiller dimensions cannot exceed the following: 1. Overall unit length: 22’-0”. 2. Chiller width including unit mounted VSD: 12'-0". 3. Chiller height: 12’-9”.