A. Provide Newage/Stamford HCI534E generators. The generators shall be rated for minimum 540kW continuous output at 105°C rise at 0.8 power factor. The generators shall be 2/3 pitch winding, 3 phase, 277/480 volt, 12 lead reconnectable, with PMG excitation. B. The generators shall be provided with adapter and coupling to mate with SAE 1 engine adapter and 14” flywheel. C. If a Marathon or other generator of equivalent or greater capacity is provided as a substitution it shall be modified and upgraded prior to delivery as follows: 1. Inspect generator internally for defects. If any defects are encountered immediately file a warranty claim with the manufacturer or provide a replacement. 2. Electrically test all windings. 3. Check fasteners for proper torque. 4. Replace diode plate mounting bolts with grade 8 bolts with nylok nuts. 5. Insulate main rotor leads with phase paper or fabric wire loom. Secure leads with heat shrinkable polyester tape using epoxy on all knots.