SPRINKLER HEADS - A. Manufacturer: Central Sprinkler Corporation, Tyco, Reliable, Star Sprinkler, Victaulic and Viking. B. Provide Sprinkler heads with appropriate response, coverage, and temperature rating. 1. Provide higher temperature sprinklers at all locations with heat source. These locations include, but are not limited to skylights, sealed display windows, in unventilated attics and roof spaces, over cooking equipment, adjacent to diffusers, unit heaters, uninsulated heating pipes or ducts, mechanical rooms, storage rooms, generator rooms, or where otherwise indicated. C. HEAD TYPES: 1. Finished Spaces: Provide concealed type with covers matching adjacent finish color. 2. Unfinished Spaces: Provide upright, pendant or sidewall sprinkler head, with brass finish with protective cage. D. Locate sprinkler heads in the center of ceiling tiles. Maintain minimum clearances from obstructions, ceilings and walls. E. Install sprinkler heads level in locations not subject to spray pattern interference. Provide fire sprinkler head installations below 56 ductwork, soffits, etc...