BASE: Total unit shall rest securely on a steel base. Vibration isolators shall be mounted between base and engine generator set (to be installed on existing pad). ENGINE: Unit shall be suited for the requirements of Line Items 1 – 16. Engine exhaust shall be routed out and equipped with rain cap. Engine shall be equipped with the following: Liquid-cooled diesel engine Electric Starting System, 12 Volt DC Exhaust Silencer, Critical Type Replaceable Fuel Filter with Water Separator Replaceable Oil Filter(s) Oil Extension Drain Replaceable Air Filter(s) Jacket Water Heater(s) (The wattage shall be as recommended by the manufacturer) 12 Volt Battery with Acid, Rack and Cables Trickle Charger, 120 VAC Input, 12 VDC Output, UL Listed, Panel Mounted ENGINE GOVERNOR: Engine speed shall be governed by an electronic type governor allowing isochronous frequency regulation and a steady state operation of + 0.25% from no load to load. FUEL TANK CAPACITY/ RUN TIME: Unit shall have a double wall construction, UL approved, minimum 189-gallon fuel tank capacity with a run time of no less than 24 hours at the 100% rated load. Shall be equipped with a locking fuel cap, extension drain, fuel level gauge and venting per UL 142 standards...