Types of work, normally recognized as electrical but provided as mechanical, specified or partially specified in this Section, include but are not necessarily limited to the following: 1. Motors for mechanical equipment. 2. Starters for motors of mechanical equipment, but only where specifically indicated to be furnished integrally with equipment. 3. Wiring from motors to disconnect switches or junction boxes for motors of mechanical equipment, but only where specifically indicated to be furnished integrally with equipment. 4. Wiring of field-mounted float control switches, flow control switches, and similar mechanical-electrical devices provided for mechanical systems, to equipment control panels. 5. Wiring of smoke detectors for shutdown of air handling equipment when a fire alarm system is not included in the project. 6. Wiring of oil pump, vibration and oil level limit switches for cooling towers. 7. Refrigerant monitor/sensor/alarming and field installed visual/audible display alarms. 8. Pipe heat tracing. 9. Cooling tower vibration switch/interlock/reset. 10. Field interlock wiring from chiller: flow switches, pump aux. Contacts, pump start/stop. 11. Power supply 120 VAC and control signal from chiller control panel to condenser water flow control valve installed in piping leaving chiller. 12. Wiring of all related circulating water system chemical treatment devices. a. Low voltage electric contacting water meter b. Solenoid valve/blow-down assembly 13. Radiant heater timer switches and/or thermostats 14. Low Voltage thermostat wiring